Work out the rate
How the rate is calculated
BS 5839-1:2025 added an Annex F with the calculation. The FIA's guide to the 2025 changes gives it as:
Afr = 100 × (Afn ÷ DAF)
- Afr is the false alarm rate, per 100 detectors per annum.
- Afn is the number of false alarms, here over the previous 12 months.
- DAF is the number of automatic fire detectors in the system.
The standard recommends working this out at every service visit, which is why it sits on the servicing checklist.
When to investigate
- Preliminary investigationWhen the rate over the previous 12 months is more than 4 false alarms per 100 detectors per annum.
- In-depth investigationFor systems with more than 40 automatic fire detectors, when the average rate is more than 5 false alarms per 100 detectors per annum.
- Every false alarm, every timeNew in 2025 (clause 29.6): the user should investigate every false alarm, and the commissioning or handover organisation should tell them how.
The trigger points are the same as in the 2017 edition, now expressed through the Annex F rate. The categories of false alarm (unwanted, equipment, malicious, good intent) moved into the commentary of clause 30, and the user is expected to put each false alarm in the right one.
Sources
- FIA: Guide to the changes in BS 5839-1:2025 (June 2025), section 20 and Annex F
- FIA: guidance on false alarms for responsible persons