How often: every 5 to 7 months
BS 5839-1:2025 (published 30 April 2025, replacing the 2017 edition) asks for periodic inspection and servicing by a competent person at intervals of about six months (clause 43.2.1). A visit any time from 5 to 7 months after the last one is acceptable, and the schedule starts from the date the system was accepted.
That tolerance is new. The 2017 edition set a maximum of six months between visits and said a system serviced less often was no longer compliant. Monthly or weekly user tests by the premises don't replace the six-monthly service.
Every visit
The core of each service, paraphrased from the standard and the FIA's guide to the 2025 changes. Your manufacturer's instructions and your certification body's rules come on top.
- Read the logbookCheck every fault and false alarm recorded since the last visit was dealt with.
- Work out the false alarm rateRecord the false alarm rate for the past 12 months: 100 × false alarms ÷ automatic detectors (new Annex F). Use the false alarm rate calculator.
- Look for changes to the building or its useNew partitions, storage up against detectors, a changed room use, a new exit without a call point.
- Check the standby batteries and chargerBattery voltage on charge, the charger's output holding up under alarm load with the battery disconnected, and the condition of the batteries.
- Prove at least one device on every circuitThe control panel receives and shows the signal, sounds the alarm and runs its other outputs. Note which devices you used.
- Check the panel's controls, indicators and fault warningsIncluding simulated faults where practicable, ancillary functions and any printer.
- Check the panel clockNew in 2025: the date and time on the control panel are checked at every visit.
- Test every signal to the alarm receiving centreNew in 2025: every type of signal sent to the ARC (fire, fault and so on), not just one. Tell the ARC before you start.
- Keep disablements to a minimumAnd tell premises management which areas are disabled while you work.
- Service radio parts as the manufacturer saysRadio devices, batteries and links, plus any other checks the manufacturer recommends.
- Leave faults showingIf a repair can't be finished, don't suppress the fault indication: report the defect to premises management in writing.
- Fill in the logbook and issue the certificateRecord the visit, the devices tested, defects and variations, then hand over the inspection and servicing certificate.
Over each 12 months
Some work can be spread across the year's visits rather than done at each one. By the end of every 12 months:
- Every manual call point testedEach one operated, by key or switch test.
- Every automatic detector functionally testedWith the right test equipment for the detector type (smoke, heat, multisensor, beam, aspirating).
- Every sounder and visual alarm device workingConfirmed at least once in the year.
- Duct smoke detectors functionally testedNew in 2025: at the 12-month visit.
- Zone identification checked against the zone planNew in 2025: at the 12-month visit.
- Remote indicators checkedAt the annual visit.
Keep a device list. The simplest way to show every device was tested in the year is a list of devices by zone with the date each was tested. Without one, nobody can prove which devices were missed.
What changed from BS 5839-1:2017
The servicing changes most likely to catch you out, from the FIA's guide to the 2025 edition:
- 5 to 7 month windowReplaces the hard six-month maximum.
- All variations in the logbook2017 asked only for "major" variations.
- Panel clock checkedAt every visit.
- Every ARC signal type testedAt every visit.
- Remote access rulesNew clause 43.4: a risk assessment before any remote session, and an authenticated connection.
- Firmware updates count as changesA control panel firmware update is a modification, so it needs a certificate.
- Faults stay visibleFault indications aren't to be suppressed when a repair can't be completed.
- "Competent person" definedClause 3.13, with a note that keeping competence up is likely to need CPD.
The logbook clause is now 48 (its model moves to Annex H). The model certificates stay in Annex G.
What the certificate and logbook record
After each visit the competent person issues an inspection and servicing certificate. BS 5839-1:2025 gives a model form in Annex G. Your own layout is fine if it records the same things:
- The premises, the system and the date of the visit.
- Which parts of the system were inspected and tested, by zone or as a share of the devices.
- Defects found and anything left outstanding.
- Variations from the standard, so the customer knows they exist (these go in the logbook too).
- Recommendations for the premises, such as false alarm reduction.
- Who did the work, for which servicing organisation, with signatures.
The logbook belongs to the premises. The responsible person keeps it up to date, near the control panel and available to the fire and rescue service. Your visit, the false alarms and every agreed variation go in it.
Third-party certification
Firms certificated under BAFE SP203-1 (through NSI, SSAIB, BSI, BRE and others) work to BS 5839-1:2025 for maintenance, and BAFE's guidance allows a combined BAFE and BS 5839-1 maintenance certificate. Lead individuals in SP203-1 firms needed a Level 3 qualification by 1 November 2025. If your certification body asks for anything extra on your certificates, its scheme documents say so.
Who has to keep it serviced
BS 5839-1 is a code of practice. The legal duty sits with the premises:
- England and Wales: article 17 of the Regulatory Reform (Fire Safety) Order 2005. The responsible person keeps fire safety equipment under a suitable system of maintenance, in efficient working order and good repair.
- Scotland: regulation 16 of the Fire Safety (Scotland) Regulations 2006.
- Northern Ireland: regulation 16 of the Fire Safety Regulations (Northern Ireland) 2010.
- High-rise flats in England: regulation 7 of the Fire Safety (England) Regulations 2022 adds monthly checks of essential fire-fighting equipment in residential buildings at least 18 m or 7 storeys high.
Following BS 5839-1 is how most responsible persons, insurers and fire officers expect that duty to be met, which is why your certificate matters to them.
Gaps that come up most
- Only "major" variations written down, as the 2017 edition allowed.
- False alarms not logged, or the rate not worked out at each visit.
- The ARC not told before testing, or only one signal type tested.
- Fault indications silenced instead of reported.
- Out-of-date text descriptors on addressable panels. Keeping them current is the premises' job, but flag it.
- The panel clock left wrong.
- Devices missed across the 12-month cycle, with no device list to show it.
Sources
This is a plain-English summary, not a copy of the standard. Check the standard itself for the full requirements: buy BS 5839-1:2025 from BSI.
- FIA: Guide to the changes in BS 5839-1:2025 (June 2025)
- BSI: updated fire alarm standard for non-domestic premises (30 April 2025)
- IET Wiring Matters: key changes to BS 5839-1:2025, part 2 (November 2025)
- FIA: logbooks and maintaining the fire alarm system
- BAFE: SP203-1 scheme FAQs
- Regulatory Reform (Fire Safety) Order 2005, article 17
- Fire Safety (Scotland) Regulations 2006, regulation 16
- Fire Safety Regulations (Northern Ireland) 2010, regulation 16
- Fire Safety (England) Regulations 2022: regulation 7 factsheet